SmartOnline 208/240, 230V 6kVA 5.4kW Double-Conversion UPS, 4U Rack/Tower, Extended Run, Network Card Options, USB, DB9 Serial, Bypass Switch, C19
Specifications
Additional Information
- UPC: 0037332157232
- Manufacturer: TRIPPLITE
- Specifications
- Output Volt Amp Capacity (VA): 6000
- Output kVA Capacity (kVA): 6.0
- Output Watt Capacity (Watts): 5400
- Output kW Capacity (kW): 5.4
- Output Capacity Details: Output capacity de-rates to 4992 watts when used at 208V with optional L6-30P line cord; Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as the overload is cleared
- Power Factor: 0.9
- Crest Factor: 3:1
- Nominal Output Voltage(s) Supported: 200V; 208V; 220V; 230V; 240V
- Nominal Voltage Details: Voltage selection via front panel LCD interface
- Frequency Compatibility: 50 / 60 Hz
- Frequency Compatibility Details: Output frequency matches input nominal on startup; Frequency conversion mode enable conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
- Output Voltage Regulation (Line Mode): +/- 2%
- Output Voltage Regulation (Economy Line Mode): +/- 10%
- Output Voltage Regulation (Battery Mode): +/- 2%
- Output Receptacles: (4) C19
- Output Receptacle Details: Output receptacle and input connections are mounted on a detachable PDU backplate with bypass switch to enable hot-swappable power module replacement
- Output Circuit Breakers: Two 20A breakers protect 2 C19 outlets each
- Output AC Waveform (AC Mode): Pure Sine wave
- Output AC Waveform (Battery Mode): Pure Sine wave
- Rated input current (Maximum Load): 31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)
- Nominal Input Voltage(s) Supported: 200V AC; 208V AC; 220V AC; 230V AC; 240V AC
- Nominal Input Voltage Description: Factory configured to 208V
- UPS Input Connection Type: Hardwire
- UPS Input Connection Description: Supports North American 208/240V input (L1,L2,G) or International 230/220/240V (L,N,PE) input wiring; Optional SU30ACORD offers NEMA L6-30P input
- Recommended Electrical Service: 40A (200/208v); 30-32A (220/230/240v)
- Input Phase: Single-Phase
- Full Load Runtime (min.): 2 minutes (5400 watts)
- Half Load Runtime (min.): 8.5 minutes (2700 watts)
- Expandable Battery Runtime: Runtime is expandable with external battery packs
- External Battery Pack Compatibility: BP192V1037C-1PH; BP192V12-3U; BP192V1407C-1PH; BP192V557C-1PH; BP192V787C-1PH
- DC System Voltage (VDC): 192
- Battery Recharge Rate (Included Batteries): 6 hours from 10% to 90% (typical, full load discharge)
- Internal UPS Replacement Battery Cartridge: RBC5-192
- Battery Access: Front panel battery access door
- Battery Replacement Description: Hot-swappable, user replaceable internal batteries
- Expandable Runtime: Yes
- Voltage Regulation Description: Online, double-conversion power conditioning
- Overvoltage Correction: Corrects overvoltages as high as 300V (<90% load) and 280V (full load)
- Undervoltage Correction: Corrects undervoltages as low as 100 (<50% load) and 155V (full load); derates linearly
- Front Panel LCD Display: Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats
- Switches: Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads.
- Alarm Cancel Operation: Alarm cancel switch
- Audible Alarm: Unique audible alarms for all major UPS, environmental and power conditions (see manual)
- LED Indicators: 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options
- UPS AC Suppression Response Time: Instantaneous
- Included Mounting Accessory Description: Includes 4 post rackmount installation accessories
- Primary Form Factor: Rackmount
- UPS Power Module Dimensions (hwd, in.): 6.85 x 17.5 x 20.67
- Rack Height (U Spaces): 4
- Maximum Device Depth (in.): 20.7
- Minimum Required Rack Depth (inches): 28.7
- UPS Power Module Weight (lbs.): 108
- UPS Power Module Weight (kg): 48.99
- UPS Shipping Dimensions (hwd / in.): 12.7 x 23.6 x 29.1
- Shipping Weight (lbs.): 156.5
- Cooling Method: Fans
- UPS Housing Material: Steel
- Minimum Required Rack Depth (mm): 729
- Primary UPS Height (mm): 174
- Primary UPS Width (mm): 444
- Primary UPS Depth (mm): 525
- Shipping Height (mm): 323
- Shipping Width (mm): 599
- Shipping Depth (mm): 739
- Operating Temperature Range: +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Storage Temperature Range: +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity: 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load): 1767
- AC Economy Mode BTU / Hr. (Full Load): 768
- Battery Mode BTU / Hr. (Full Load): 2279
- AC Mode Efficiency Rating (100% Load): 90%
- AC Economy Mode Efficiency Rating (100% Load): 96%
- Operating Elevation (ft.): 0-3000m (0 to 10,000 ft.)
- Audible Noise: 60 dBA at front side 1 meter
- Operating Elevation (msnm): 0-3000 m
- Communications Interface: USB
- Network Management Cards: SNMPWEBCARD; TLNETCARD; WEBCARDLX; MODBUSCARD; RELAYIOCARD
- Network Monitoring Port Description: Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports
- PowerAlert Software: For local monitoring via the UPSs built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable: USB, DB9 serial and EPO cables included
- WatchDog Compatibility: Yes
- Transfer Time: No transfer time (0 ms.) in online, double-conversion mode
- Transfer Time (Economy Mode): 8 ms. typical power failure response in optional economy mode
- Low Voltage Transfer to Battery Power (Setpoint): 156V (full load) / 100V (50% load or less, derates linearly)
- High Voltage Transfer to Battery Power (Setpoint): 280V (full load) / 300V (90% load or less)
- Cold Start (Startup in Battery Mode During a Power Failure): Cold-start operation supported
- UPS Certifications: CE; Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances); Tested to CSA (Canada); Tested to UL1778 (USA)
- UPS Certification Details: IEC 61000-4-5 1995 B Surge Immunity
- Product Warranty Period (Worldwide): 2-year limited warranty
- Connected Equipment Insurance (U.S., Canada & Puerto Rico): $250,000 Ultimate Lifetime Insurance
- Downloads: ""
- Manufacturer Product URL: https://www.tripplite.com/smartonline-208-240-230v-6kva-5.4kw-double-conversion-ups-4u-rack-tower-extended-run-snmpwebcard-option-usb-db9-serial-bypass-switch-c19~SU6000RT4UHVG/
- Packaging
- Certifications
- Details: "Overview\nTripp Lite SU6000RT4UHVG 6000VA \/ 6kVA \/ 5400 watt on-line, double-conversion UPS system offers complete power protection for critical server, network and telecommunications equipment in a single 4U rack\/tower compatible housing. Full-time active power conditioning provides clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise. Fault-tolerant auto-bypass prevents unexpected service interruptions during UPS overload or internal fault conditions. Detachable back panel PDU with manual bypass switch supports hot-swappable whole UPS replacement with no interruption to connected equipment. Single all-in-one rack \/ tower housing installs in only 4 rack spaces (4U) with a maximum installed depth of only 20.7 in. \/ 52.6cm. Maintains full-time sine wave output within 2% of selectable 200\/208\/220\/230\/240V nominal during brownouts as low 100V and overvoltages as high as 300V. Expandable runtime is supported with optional BP192V12-3U external battery packs. Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement. Double-conversion operation converts raw input from AC to DC, then re-synthesizes output power back to perfect sine wave AC with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types. Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs. Network-grade AC surge and noise suppression. Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces. Optional network management card options available. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as UPS batteries become depleted. Supports Emergency Power Off (EPO) via built-in interface. Front panel LEDs and LCD readout with scroll controls support front-panel visual monitoring of all major UPS for a variety of control options to support advanced UPS settings and configurations. LED \/ LCD display panel rotates for viewing in rackmount or tower configurations. Hardwire input and 4 C19 outlets. Support for optional North American and International cordsets. External battery packs are field replaceable and hot swappable."
- List price: No