- Specifications
- Output Volt Amp Capacity (VA): 3000
- Output kVA Capacity (kVA): 3
- Output Watt Capacity (Watts): 2400
- Output kW Capacity (kW): 2.4
- Output Capacity Details: OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits)
- Power Factor: 0.8
- Crest Factor: 3:1
- Nominal Output Voltage(s) Supported: 110V; 120V
- Nominal Voltage Details: 120V default
- Frequency Compatibility: 50 / 60 Hz
- Frequency Compatibility Details: Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
- Output Voltage Regulation (Line Mode): +/- 2%
- Output Voltage Regulation (Economy Line Mode): +/- 10%
- Output Voltage Regulation (Battery Mode): +/- 2%
- Output Receptacles: (4) 5-15R; (4) 5-15/20R; (1) L5-30R
- Load Management Receptacles: Two switchable four-outlet load banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)
- Output Circuit Breakers: 15A branch rated (x2) - each breaker protects 4 outlets, L5-30R is unbreakered
- Output AC Waveform (AC Mode): Pure Sine wave
- Output AC Waveform (Battery Mode): Pure Sine wave
- Rated input current (Maximum Load): 24A
- Nominal Input Voltage(s) Supported: 110V AC; 120V AC
- UPS Input Connection Type: L5-30P
- Input Circuit Breakers: 40A
- UPS Input Cord Length (ft.): 10
- Recommended Electrical Service: 30A 120V
- Input Phase: Single-Phase
- Full Load Runtime (min.): 5 min. (2400w)
- Half Load Runtime (min.): 14 min. (1200w)
- Expandable Battery Runtime: Supports extended runtime with optional external battery packs
- External Battery Pack Compatibility: BP72V15-2U(limit 1); BP72V28RT-3U(multi-pack compatible); BP72V18-2US(multi-pack compatible)
- DC System Voltage (VDC): 72
- Battery Recharge Rate (Included Batteries): Less than 6 hours from 10% to 80% (typical, full load discharge)
- Internal UPS Replacement Battery Cartridge: RBC96-3U(quantity 1)
- Battery Access: Front panel battery access door
- Battery Replacement Description: Hot-swappable, user replaceable batteries
- Expandable Runtime: Yes
- Voltage Regulation Description: Online, double-conversion power conditioning
- Overvoltage Correction: 2% output voltage regulation during overvoltages to 150
- Undervoltage Correction: 2% output voltage regulation during undervoltages to 80
- Severe Undervoltage Correction: 2% output voltage regulation during undervoltages to 65 (under 70% load only)
- Switches: 2 switches control off/on power status and alarm-cancel/self-test operation
- Alarm Cancel Operation: Power-fail alarm can be silenced using alarm-cancel switch
- Audible Alarm: Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
- LED Indicators: 14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats
- UPS AC Suppression Joule Rating: 510
- UPS AC Suppression Response Time: Instantaneous
- UPS Dataline Suppression: 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
- EMI / RFI AC Noise Suppression: Yes
- Included Mounting Accessory Description: Includes 4 post rackmount installation accessories
- Installation Form Factors Supported with Optional Accessories: 2 post rackmount(2POSTRMKITHD); Tower(2-9USTAND)
- Primary Form Factor: Rackmount
- UPS Power Module Dimensions (hwd, in.): 5.2 x 17.8 x 26
- Rack Height (U Spaces): 3
- Minimum Required Rack Depth (inches): 37
- UPS Power Module Weight (lbs.): 73.8
- UPS Power Module Weight (kg): 33.48
- UPS Shipping Dimensions (hwd / in.): 11.2 x 23 x 31.5
- Shipping Weight (lbs.): 112.4
- Cooling Method: Fan
- UPS Housing Material: Steel
- Minimum Required Rack Depth (mm): 940
- Primary UPS Height (mm): 132
- Primary UPS Width (mm): 452
- Primary UPS Depth (mm): 660
- Shipping Height (mm): 284
- Shipping Width (mm): 584
- Shipping Depth (mm): 800
- Operating Temperature Range: +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Storage Temperature Range: +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity: 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load): 1117
- AC Economy Mode BTU / Hr. (Full Load): 523
- Battery Mode BTU / Hr. (Full Load): 1224
- AC Economy Mode Efficiency Rating (100% Load): 94%
- Communications Interface: USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
- Network Management Cards: SNMPWEBCARD; TLNETCARD; WEBCARDLX; MODBUSCARD; RELAYIOCARD
- Network Monitoring Port Description: Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications; Economy-mode setting option is available using PowerAlert software and DB9 Serial cable connection OR via select Network Management Card options
- PowerAlert Software: For local monitoring via the UPSs built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable: USB and DB9 cabling included
- WatchDog Compatibility: Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Transfer Time: No transfer time (0 ms.) in online, double-conversion mode
- Low Voltage Transfer to Battery Power (Setpoint): 80V (100% load), 65V ( <70% load)
- High Voltage Transfer to Battery Power (Setpoint): 150
- Cold Start (Startup in Battery Mode During a Power Failure): Cold-start operation supported
- High Availability UPS Features: Automatic inverter bypass; Hot swappable batteries
- Green Energy-Saving Features: High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation
- UPS Certifications: Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
- Product Warranty Period (Worldwide): 2-year limited warranty
- Connected Equipment Insurance (U.S., Canada & Puerto Rico): $250,000 Ultimate Lifetime Insurance
- Downloads: {"documents":[{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Owners-Manual\/932471.pdf","title":"Owner's Manual for SmartOnline Rack\/Tower UPS 932471"},{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Owners-Manual\/932766.pdf","title":"Owner's Manual Addendum for External Battery Packs 932766 (Multi-langauge)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Runtime-Chart\/SU3000RTXL3U-Runtime-Chart-EN.pdf","title":"SU3000RTXL3U runtime chart"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/Brochure\/Tripp-Lite-Integrated-Solutions-Brochure-9533AD-EN-Domestic.pdf","title":"Integrated Solutions Brochure 953479 (English)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/White-Paper\/Common-Power-Problems-and-Power-Protection-Solutions-White-Paper-EN.pdf","title":"Common Power Problems and Power Protection Solutions White Paper 120v (English)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/White-Paper\/Common-Power-Problems-and-Power-Protection-Solutions-White-Paper-230v-EN.pdf","title":"Common Power Problems and Power Protection Solutions White Paper 230v (English)"}],"miscellanous":[{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/Brochure\/UPS-Systems-Brochure-9533B9-EN-120V.PDF","title":"UPS Systems 120V Brochure 953426 (English)"},{"url":"https:https:\/\/www.tripplite.com\/products\/ups-buying-guide","title":"UPS Systems Buying Guide"},{"url":"https:https:\/\/www.tripplite.com\/products\/single-vs3-phase","title":"Single-Phase vs. 3-Phase Power"},{"url":"https:https:\/\/www.tripplite.com\/products\/custom-products","title":"Custom Products from Tripp Lite Are One Call Away"},{"url":"https:https:\/\/www.tripplite.com\/products\/economy-mode","title":"Economy Mode Explained"},{"url":"https:https:\/\/www.tripplite.com\/support\/articles\/articleid\/top-12-questions-when-choosing-a-network-ups","title":"Top 12 Questions to Consider When Choosing UPS Systems for Network\/Server Applications"},{"url":"https:https:\/\/www.tripplite.com\/products\/ups-sizing","title":"UPS Sizing"},{"url":"https:https:\/\/www.tripplite.com\/resellers\/case-study\/csid\/loma-linda-ups-for-hospitals","title":"Loma Linda UPS for Hospitals"},{"url":"https:https:\/\/www.tripplite.com\/resellers\/imageSearch\/mid\/3023","title":"Download images for this product"}]}
- Manufacturer Product URL: https://www.tripplite.com/smartonline-120v-3kva-2.4kw-double-conversion-ups-3u-rack-tower-extended-run-snmpwebcard-option-usb-db9-serial~SU3000RTXL3U/
- Packaging
- Certifications
- Details: "Overview\n3000VA on-line, double-conversion UPS system for critical server, network and telecommunications equipment. 3U rackmount form factor with an installed depth of 26 inches. Expandable battery runtime with optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack compatible) external battery packs. Full time sine wave 110 or 120V output with +\/-2% voltage regulation. Online, double-conversion Uninterruptible Power Supply (UPS) actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output. Operates continuously without using battery power during brownouts to 65V and overvoltages to 150V. Highly efficient operation in optional economy mode saves BTU heat output and energy costs. NEMA L5-30P input plug. NEMA 5-15, NEMA 5-15\/20R and NEMA L5-30R output receptacles. Network-grade AC surge and noise suppression. Zero transfer time between AC and battery operation. Network management interfaces support simultaneous communications via USB port, DB9 serial port and slot for network management card options. Built-in DB9 port offers both enhanced RS-232 enabled monitoring data, plus contact closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions via all 3 network interfaces. PowerAlert UPS monitoring software is available via free download. Emergency Power Off (EPO) interface. Integrated two-bank PDU switching supports load shedding and remote reboot of connected equipment. 3-stage metered current monitoring and battery charge status LEDs. LED display panel easily rotates for viewing in rackmount or tower configurations. Dataline surge suppression for dialup, DSL or network Ethernet connection. Utility power and voltage regulation LEDs. Audible alarm. Self-test. Fault-tolerant auto-bypass mode. 4-post rackmount accessories included; 2-9USTAND tower kit and 2POSTRMKITHD 2-post rackmount accessories available. Field-replaceable, hot-swappable internal batteries and external battery packs. Attractive all-black color scheme.$250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only)."
- List price: No