Specifications
Additional Information
- UPC: 37332156310
- Manufacturer: TRIPPLITE
- Specifications
- Output Volt Amp Capacity (VA): 2200
- Output kVA Capacity (kVA): 2.2
- Output Watt Capacity (Watts): 1920
- Output kW Capacity (kW): 1.92
- Power Factor: 0.87
- Nominal Output Voltage(s) Supported: 120V
- Frequency Compatibility: 50 / 60 Hz
- Frequency Compatibility Details: Automatic frequency selection
- Output Voltage Regulation (Battery Mode): +/- 5%
- Output Receptacles: (4) 5-15R; (4) 5-15/20R
- Load Management Receptacles: Two switchable single-outlet 5-15R load banks
- Output AC Waveform (AC Mode): Sine wave
- Output AC Waveform (Battery Mode): Pure Sine wave
- Rated input current (Maximum Load): 16A (120V), 10A (230V)
- Nominal Input Voltage(s) Supported: 120V AC; 230V AC
- UPS Input Connection Type: 5-20P; C20 inlet
- UPS Input Connection Description: C20 inlet and 5 compatible plugsets (5-20P, Schuko CEE7, EU1-16P, British BS1363, Italian CEI 23-16)
- Input Circuit Breakers: 20A
- UPS Input Cord Length (ft.): 6
- Input Phase: Single-Phase
- Full Load Runtime (min.): 12 minutes (1920 watts)
- Half Load Runtime (min.): 30 minutes (960 watts)
- Expandable Battery Runtime: Extended runtime supported via optional external battery packs
- External Battery Pack Compatibility: BP48V24-2U(limit 1); BP48V60RT-3U(multi-pack compatible); BP48V27-2US(multi-pack compatible)
- DC System Voltage (VDC): 48
- Battery Recharge Rate (Included Batteries): Less than 4.5 hours from 10% to 90% (internal batteries)
- Internal UPS Replacement Battery Cartridge: RBC49-DV(quantity 2 required)
- Battery Access: Front panel battery access door
- Battery Replacement Description: Hot-swappable, user replaceable batteries
- Expandable Runtime: Yes
- Voltage Regulation Description: Automatic voltage regulation (AVR) maintains 120v line power output with input range of 89 to 148 or 170 to 286
- Overvoltage Correction: Voltage reduction of 12% applies when input is between 127 and 148 (120V)
- Undervoltage Correction: Voltage boost of 12% applies when input voltage is between 96 and 108 (120V)
- Switches: 2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support nominal voltage selection
- Alarm Cancel Operation: Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
- Audible Alarm: Audible alarm indicates power-failure, overload and low-battery conditions
- LED Indicators: 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
- UPS AC Suppression Joule Rating: 340
- UPS AC Suppression Response Time: Instantaneous
- EMI / RFI AC Noise Suppression: Yes
- Included Mounting Accessory Description: Complete installation accessories available for 2 post, 4 post and tower installation
- Installation Form Factors Supported with Included Accessories: Tower
- Installation Form Factors Supported with Optional Accessories: 4 post rackmount(4POSTRAILKIT)
- Primary Form Factor: Rackmount
- UPS Power Module Dimensions (hwd, in.): 5.25 x 17.5 x 25.25
- Rack Height (U Spaces): 3
- Minimum Required Rack Depth (inches): 32.3
- UPS Power Module Weight (lbs.): 104.25
- UPS Power Module Weight (kg): 47.29
- UPS Shipping Dimensions (hwd / in.): 11.5 x 29.5 x 30.5
- Shipping Weight (lbs.): 159.5
- Cooling Method: Fan
- UPS Housing Material: Steel
- Minimum Required Rack Depth (mm): 820
- Primary UPS Height (mm): 133
- Primary UPS Width (mm): 444
- Primary UPS Depth (mm): 641
- Shipping Height (mm): 292
- Shipping Width (mm): 749
- Shipping Depth (mm): 775
- Operating Temperature Range: +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
- Storage Temperature Range: +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
- Relative Humidity: 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load): 347
- Battery Mode BTU / Hr. (Full Load): 894
- AC Mode Efficiency Rating (100% Load): 95%
- Communications Interface: USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
- Network Management Cards: SNMPWEBCARD; WEBCARDLX
- Network Monitoring Port Description: Supports detailed monitoring of UPS and site power conditions
- PowerAlert Software: For local monitoring via the UPSs built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable: USB and DB9 cabling included
- WatchDog Compatibility: Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Network UPS Tools Compatibility: NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite
- Transfer Time: 2-4 milliseconds
- Low Voltage Transfer to Battery Power (Setpoint): 89 (120V), 170 (230V)
- High Voltage Transfer to Battery Power (Setpoint): 148 (120V), 286 (230V)
- Cold Start (Startup in Battery Mode During a Power Failure): Cold-start operation supported
- High Availability UPS Features: Hot swappable batteries
- Green Energy-Saving Features: Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
- UPS Certifications: Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances); TAA Compliant
- Product Warranty Period (Worldwide): 2-year limited warranty
- Downloads: {"documents":[{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Owners-Manual\/932755.pdf","title":"Quick Start Guide for PowerAlert Power Management Software 932755"},{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Owners-Manual\/932766.pdf","title":"Owner's Manual Addendum for External Battery Packs 932766 (Multi-langauge)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Owners-Manual\/932968.pdf","title":"Owner's Manual for Dual Voltage SmartPro Rackmount UPS 932968 (Multi-language)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Runtime-Chart\/SM2200RMDVTAA-Runtime-Chart-EN.pdf","title":"SM2200RMDVTAA runtime chart"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/Brochure\/TAA-Compliaint-IT-Solutions-Flyer-EN.pdf","title":"TAA Compliant IT Solutions for Government Procurement Brochure 95343F (English)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/Brochure\/Tripp-Lite-Integrated-Solutions-Brochure-9533AD-EN-Domestic.pdf","title":"Integrated Solutions Brochure 953479 (English)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/White-Paper\/Common-Power-Problems-and-Power-Protection-Solutions-White-Paper-EN.pdf","title":"Common Power Problems and Power Protection Solutions White Paper 120v (English)"}],"miscellanous":[{"url":"https:https:\/\/www.tripplite.com\/products\/ups-buying-guide","title":"UPS Systems Buying Guide"},{"url":"https:https:\/\/www.tripplite.com\/products\/single-vs3-phase","title":"Single-Phase vs. 3-Phase Power"},{"url":"https:https:\/\/www.tripplite.com\/products\/custom-products","title":"Custom Products from Tripp Lite Are One Call Away"},{"url":"https:https:\/\/www.tripplite.com\/products\/economy-mode","title":"Economy Mode Explained"},{"url":"https:https:\/\/www.tripplite.com\/pages\/taa-compliance","title":"TAA-Compliant IT Products"},{"url":"https:https:\/\/www.tripplite.com\/products\/ups-sizing","title":"UPS Sizing"},{"url":"https:https:\/\/www.tripplite.com\/resellers\/imageSearch\/mid\/4648","title":"Download images for this product"}]}
- Manufacturer Product URL: https://www.tripplite.com/taa-smartpro-120v-2.2kva-1.92kw-line-interactive-sine-wave-ups-3u-120-230v-input-network-card-options-usb-db9~SM2200RMDVTAA/
- Packaging
- Certifications
- Details: "Overview\nTripp Lite's dual input voltage SM2200RMDVTAA line interactive UPS system maintains 120V nominal output when powered by North American 120V or International 230V input. Protects a variety of computer, networking and other sensitive equipment types from blackouts, voltage fluctuations and transient surges. 3U rack \/ tower form factor with an installed depth of only 22.5 inches. Expandable battery runtime with optional BP48V24-2U and BP48V60RT3U external battery packs. Uninterruptible Power Supply (UPS) switches to battery-derived AC output during power failures and extreme voltage variations. Line interactive Automatic Voltage Regulation (AVR) offers voltage boost during brownouts and voltage cut during overvoltages to maintain regulated 120v output over an input range of 89 to 148V or 212 to 286V. Includes C20 power inlet with set of 4 international cord sets and both NEMA 5-15R and 5-15\/20R output receptacles. Network-grade AC surge and noise suppression. Communications interfaces support communications via USB, DB9 serial and slot for optional network management card. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions via all 3 network interfaces. PowerAlert monitoring software is available via free download. Emergency Power Off (EPO) interface. Integrated 2-bank programmable PDU switching supports load shedding and remote-reboot of up to 2 individual connected devices. 3-stage metered current monitoring and battery charge status LEDs. 95% efficiency in line power mode reduces energy cost and BTU emissions. Utility power and voltage regulation LEDs. Audible alarm. Self-test. Installation accessories for rackmount and upright tower form factors included. Field-replaceable, hot-swappable internal batteries and external battery packs. Attractive all-black color scheme."
- List price: No