SmartOnline 120V 2.2kVA 1.6kW Double-Conversion UPS, 2U Rack/Tower, Extended Run, Pre-installed Network Management Card, USB, DB9 Serial
Specifications
Additional Information
- UPC: 37332181480
- Manufacturer: TRIPPLITE
- Specifications
- Output Volt Amp Capacity (VA): 2200
- Output kVA Capacity (kVA): 2.2
- Output Watt Capacity (Watts): 1600
- Output kW Capacity (kW): 1.6
- Output Capacity Details: OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits)
- Power Factor: 0.7
- Crest Factor: 3:1
- Nominal Output Voltage(s) Supported: 110V; 120V
- Nominal Voltage Details: 120V default
- Frequency Compatibility: 50 / 60 Hz
- Frequency Compatibility Details: Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
- Output Voltage Regulation (Line Mode): +/- 2%
- Output Voltage Regulation (Economy Line Mode): +/- 10%
- Output Voltage Regulation (Battery Mode): +/- 2%
- Output Receptacles: (6) 5-15/20R; (1) L5-20R
- Load Management Receptacles: Two switchable three-outlet 5-15/20R load banks
- Output AC Waveform (AC Mode): Sine wave
- Output AC Waveform (Battery Mode): Pure Sine wave
- Rated input current (Maximum Load): 16A
- Nominal Input Voltage(s) Supported: 110V AC; 120V AC
- UPS Input Connection Type: 5-20P
- Input Circuit Breakers: 30A
- UPS Input Cord Length (ft.): 10
- UPS Input Cord Length Details: Built-in
- Recommended Electrical Service: 20A 120V
- Input Phase: Single-Phase
- Full Load Runtime (min.): 4.5 min. (1600w)
- Half Load Runtime (min.): 14 min. (800w)
- Expandable Battery Runtime: Extended runtime supported via optional external battery packs
- External Battery Pack Compatibility: BP48V24-2U(limit 1); BP48V60RT-3U(multi-pack compatible); BP48V27-2US(multi-pack compatible)
- Expandable Runtime Description: BP48V24-2U(limit 2 w/ 48VDCSPLITTER)
- DC System Voltage (VDC): 48
- Battery Recharge Rate (Included Batteries): Less than 6 hours from 10% to 80% (typical, full load discharge)
- Internal UPS Replacement Battery Cartridge: RBC94-2U
- Battery Access: Front panel battery access door
- Battery Replacement Description: Hot-swappable, user replaceable sealed, flame retardant, non-spillable batteries
- Expandable Runtime: Yes
- Voltage Regulation Description: Online, double-conversion power conditioning
- Overvoltage Correction: 2% output voltage regulation during overvoltages to 150
- Undervoltage Correction: 2% output voltage regulation during undervoltages to 80
- Severe Undervoltage Correction: 2% output voltage regulation during undervoltages to 65 (under 70% load only)
- Switches: 2 switches control off/on power status and alarm-cancel/self-test operation
- Alarm Cancel Operation: Power-fail alarm can be silenced using alarm-cancel switch
- Audible Alarm: Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
- LED Indicators: 14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats
- UPS AC Suppression Joule Rating: 570
- UPS AC Suppression Response Time: Instantaneous
- UPS Dataline Suppression: 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
- EMI / RFI AC Noise Suppression: Yes
- Included Mounting Accessory Description: Includes 4 post rackmount installation accessories
- Installation Form Factors Supported with Optional Accessories: 2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND)
- Primary Form Factor: Rackmount
- UPS Power Module Dimensions (hwd, in.): 3.5 x 17.5 x 19
- Rack Height (U Spaces): 2
- Minimum Required Rack Depth (inches): 26
- UPS Power Module Weight (lbs.): 47.4
- UPS Power Module Weight (kg): 21.50
- UPS Shipping Dimensions (hwd / in.): 9.8 x 20.2 x 24
- Shipping Weight (lbs.): 57.3
- Cooling Method: Fan
- UPS Housing Material: Steel
- Minimum Required Rack Depth (mm): 660
- Primary UPS Height (mm): 89
- Primary UPS Width (mm): 444
- Primary UPS Depth (mm): 483
- Shipping Height (mm): 249
- Shipping Width (mm): 513
- Shipping Depth (mm): 610
- Operating Temperature Range: +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Storage Temperature Range: +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity: 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load): 816
- AC Economy Mode BTU / Hr. (Full Load): 349
- Battery Mode BTU / Hr. (Full Load): 889
- AC Economy Mode Efficiency Rating (100% Load): 94%
- Audible Noise: < 45dB at 1m
- Communications Interface: Contact closure; DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface; USB (HID enabled)
- Network Monitoring Port Description: Includes pre-installed Network Management Card; DB9 port supports RS232 and contact closure communications; Economy-mode setting option is available using PowerAlert software and DB9 Serial cable connection OR installed Network Management Card
- PowerAlert Software: For local monitoring via the UPSs built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable: USB and DB9 cabling included
- WatchDog Compatibility: Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Transfer Time: No transfer time (0 ms.) in online, double-conversion mode
- Low Voltage Transfer to Battery Power (Setpoint): 80V (100% load), 65V ( <70% load)
- High Voltage Transfer to Battery Power (Setpoint): 150
- Cold Start (Startup in Battery Mode During a Power Failure): Cold-start operation supported
- High Availability UPS Features: Automatic inverter bypass; Hot swappable batteries
- Green Energy-Saving Features: High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation
- UPS Certifications: Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
- Product Warranty Period (Worldwide): 2-year limited warranty
- Connected Equipment Insurance (U.S., Canada & Puerto Rico): $250,000 Ultimate Lifetime Insurance
- Downloads: {"documents":[{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Owners-Manual\/932471.pdf","title":"Owner's Manual for SmartOnline Rack\/Tower UPS 932471"},{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Owners-Manual\/932766.pdf","title":"Owner's Manual Addendum for External Battery Packs 932766 (Multi-langauge)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Owners-Manual\/933000.pdf","title":"Installation Guide for Select Rackmount UPS 933000"},{"url":"https:https:\/\/www.tripplite.com\/shared\/techdoc\/Runtime-Chart\/SU2200RTXL2UN-Runtime-Chart-EN.pdf","title":"SU2200RTXL2UN runtime chart"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/Brochure\/Tripp-Lite-Integrated-Solutions-Brochure-9533AD-EN-Domestic.pdf","title":"Integrated Solutions Brochure 953479 (English)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/White-Paper\/Common-Power-Problems-and-Power-Protection-Solutions-White-Paper-EN.pdf","title":"Common Power Problems and Power Protection Solutions White Paper 120v (English)"},{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/White-Paper\/Common-Power-Problems-and-Power-Protection-Solutions-White-Paper-230v-EN.pdf","title":"Common Power Problems and Power Protection Solutions White Paper 230v (English)"}],"miscellanous":[{"url":"https:https:\/\/www.tripplite.com\/shared\/literature\/Brochure\/UPS-Systems-Brochure-9533B9-EN-120V.PDF","title":"UPS Systems 120V Brochure 953426 (English)"},{"url":"https:https:\/\/www.tripplite.com\/products\/ups-buying-guide","title":"UPS Systems Buying Guide"},{"url":"https:https:\/\/www.tripplite.com\/products\/single-vs3-phase","title":"Single-Phase vs. 3-Phase Power"},{"url":"https:https:\/\/www.tripplite.com\/products\/custom-products","title":"Custom Products from Tripp Lite Are One Call Away"},{"url":"https:https:\/\/www.tripplite.com\/products\/economy-mode","title":"Economy Mode Explained"},{"url":"https:https:\/\/www.tripplite.com\/support\/articles\/articleid\/top-12-questions-when-choosing-a-network-ups","title":"Top 12 Questions to Consider When Choosing UPS Systems for Network\/Server Applications"},{"url":"https:https:\/\/www.tripplite.com\/products\/ups-sizing","title":"UPS Sizing"},{"url":"https:https:\/\/www.tripplite.com\/resellers\/imageSearch\/mid\/5685","title":"Download images for this product"}]}
- Manufacturer Product URL: https://www.tripplite.com/smartonline-120v-2.2kva-1.6kw-double-conversion-ups-2u-rack-tower-extended-run-pre-installed-snmpwebcard-usb-db9-serial~SU2200RTXL2UN/
- Packaging
- Certifications
- Details: "Overview\nTripp Lite Smart Online UPS systems offer high performance power protection ideal for critical server and network equipment in datacenters, computer rooms and network closets. Online, double-conversion Uninterruptible Power Supply (UPS) maintains perfectly regulated output power by continuously converting raw AC input to DC, then re-converting output back to AC. Fully regulated sine wave AC output with +\/-2% voltage regulation powers network equipment continuously, even during severe brownouts and overvoltages, all without depleting UPS battery reserves. Maintains battery-derived AC output during power failures with zero transfer time. Extended runtime options available. Highly efficient operation in optional economy mode saves BTU heat output and energy costs. Network management interfaces support communications via USB, RS-232, contact-closure and pre-installed Network Management Card interface. Built-in DB9 port offers both enhanced RS-232 data and basic contact closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. PowerAlert UPS monitoring software is available via free download. Emergency Power Off (EPO) interface. LED display reports UPS operating mode, line power availability, battery mode operation, inverter operation and output power availability. Audible alarm with push-button momentary alarm-cancel. Programmable self-test. Fault-tolerant auto-bypass mode. Field-replaceable, hot-swappable internal batteries and external battery packs."
- List price: No